8
GENERAL SPECIFICATIONS
5 Amp CURRENT INPUTS
Continuous rating: 20A
One Sec. Rating: 400A
Saturation limit: 150A
Burden: <10milliohms
1 Amp CURRENT INPUTS
Continuous rating: 4A
One Sec. rating: 80A
Saturation limit: 30A
Burden: <22milliohms
PHASE AC VOLTAGE INPUTS
Continuous: 300V, Line to Line
One Sec. rating: 600V, Line to Neutral
Burden: Less than 1VA @ 300Vac
AUXILIARY AC VOLTAGE INPUT (V
x
)
Continuous: 150V
One Sec. rating: 600V
Burden: Less than 1VA @ 150Vac
A/D CONVERTER
Sampling Rate: 32/cycle, adjusted to
input frequency 10-75Hz
POWER SUPPLY
Option 1: 48/125Vac/dc DC range 35-150V
AC range 55-135V
Option 2: 125/250Vac/dc DC range 90 - 300V
AC range 90 - 270V
Option 3: 24Vdc DC range 17 - 32V
(down to 8V for momentary dips)
Burden: 10 Watts continuous,
12 Watts maximum with
all outputs energized
TRIP CONTACTS
Make and carry: 30A (0.2sec)
Continuous: 7A
Break: 0.3A DC (L/R=0.04)
CONTROL INPUTS
Wetting voltage range:
Low Range High Range
Turn-on Turn-on
Power Supply Voltage Voltage
Option Range Burden Range Burden
1) 48/125Vac/Vdc 26-38V 123.76k ohms 69-100V 66.49k ohms
2) 125/250Vac/Vdc 69-100V 53.65k ohms 138-200V 21.15k ohms
3) 24Vdc 5-8Vdc 6.15k ohms N/A N/A
Control inputs recognize both DC and AC voltages.
COMMUNICATION PORTS
Response time: <100mSec for metering
and control functions
Baud rate: Up to 115,200
ELECTRICAL ENVIRONMENT
IEEE C37.90-1989 Standard for Relays and Relay
Systems Associated with Electric Power Apparatus
IEC 255-5 Insulation Test for Electrical Relays
Impulse and Dielectric Strength (2000Vac at 50/60Hz)
IEEE C37.90.1-1989 Standard Surge Withstand Cap-
ability Tests for Relays and Relay Systems Associated
with Electric Power Apparatus
IEC 255-22-1 1MHz Burst Disturbance Tests for Elec-
trical Disturbance Tests for Measuring Relays and
Protection Equipment
EN 61000-4-4 Electrical Fast Transient/Burst Immunity
Test
EN 61000-4-3 Radiated, Radio-frequency, Electro-
magnetic Field Immunity Test
Type tested using a 5-watt, hand-held transceiver in
the ranges of 144 and 440MHz with the antenna
placed within 6 inches of the relay.
IEEE C37.90.3 (Jan. 01) Draft Standard Electrostatic
Discharge Tests for Protective Relays
EN 61000-4-2 Electrostatic Discharge Immunity Test
MECHANICAL ENVIRONMENT
Operating temperature range: -40°C to 70°C*
(-40°F to 158°F)
*LCD Display is inoperative below -20°C.
Storage temperature range: -40°C to 70°C
(-40°F to 158°F)
Humidity: Qualified to IEC 68-2-38, 1st Edition
1974, Basic Environmental Test Procedures,
Part 2: Test Z/AD: Composite Temperature
Humidity Cyclic Test
Qualified to IEC 255-21-1 (Class 1) Vibration Tests
for Electrical Relays
Qualified to IEC 255-21-2 (Class 1) Shock and
Bump Tests for Electrical Relays
CERTIFICATIONS
UL recognized per Standard 508, File E97033
CSA certified per Standard CAN/CSA-C22-2
Gost R certified per relevant standards of
Gosstandart of Russia
CE qualified - meets or exceeds standards for
distribution in the European Community
CASE SIZE
10.50"W x 3.47"H x 9.10"D with mounting flanges
(8.5"W without mounting flanges)
SHIPPING WEIGHT
Approx. 12 pounds (5.4 kg)
WARRANTY
7 years