APPLICATIONS
The BE1-11g Generator Protection System provides the three phase, ground, and negative sequence overcurrent,
voltage, over/under or rate-of-change of frequency, directional power, loss of excitation, overexcitation, and sync
check functions for use in generator protection applications. The unit also may be used in any directional or
nondirectional overcurrent application that requires frequency and overexcitation protection and that does not also
require a reclosing function. The specialized capabilities of this protective system make it ideally suited for these
applications:
• Applications that require the flexibility provided by wide setting ranges, a large number of elements, multiple
setting groups, multiple coordination curves, and the versatility of visual programmable logic, in a single com-
pact package.
• Applications that require an economic unit with a space-conscious package. The 11g can provide all of the
protection, control, instrumentation, and communications required in many installations.
• Applications where small size and limited behind-panel projection facilities are required to modernize an existing
installation.
• Applications that require high speed Ethernet communications, copper or fiber.
• Applications where drawout construction is required.
FEATURES, continued
Figure 1 - Advanced HMI (Human Machine Interface)
• More than 20 additional alarm points, user program-
mable for major or minor priority. Including:
- Phase current, forward and reverse Watt and Var
demand alarm
- Neutral and negative sequence unbalance demand
- Three breaker alarm points programmable for slow
trip, interruption duty threshold, or operations counter
- Trip circuit voltage and continuity monitor
- Close circuit monitor via BESTLogicPlus
PROGRAMMABLE I/O
• Four programmable inputs
• Five programmable outputs and one dedicated
programmable alarm output
HARDWARE FEATURES
• Case configuration - H1: Half Rack
• Active CT technology for low burden and in
creased
dynamic range
• Flash Memory for upgrading embedded programming
• Real Time Clock with 8 hour capacitor ride through and
battery backup
• Integral HMI with 128x64 character display
• Wide range ac/dc power supply options provide long
holdup time to ride through dips on ac power source.
100 ms with 4 output relays energized, upon complete
loss of source. Starting voltage 125Vac for Option 1
(48/125Vac/dc) and 250Vac for Option 2
(125/250Vac/dc)).