BE1-87G
Two Types of Targets
Page 1-6
Internally operated or current operated targets
Internally operated–electronically latching
• Manual-reset targets indicate that a setpoint
contact has energized.
• Select internally operated targets if the relay has
normally closed output contacts.
Current-operated
• Require a minimum trip circuit current of 200 mA
› Continuous rating of 3 amperes
› Two-minute rating of 7 amperes
› One-second rating of 30 amperes